Technical Bulletin
Fire Phase I (Recall) Door Operation with Walk Through
Doors
Safety Issue--Immediate Action
Date
January 23, 2002
Reference
128
Route to
Service Manager/Modernization Manager
From
MCE Technical Support Department
Equipment
IMC, PTC, PHC, VVMC or VFMC controllers with BOTH constant
pressure door closing operation AND walk through doors at the
main or alternate fire floor.
Description
According to elevator codes, if a car with walk through doors is
at a fire floor and the Fire Phase 1 (Recall) is activated, the
designated door must open or remain open, and the opposite door
should close or remain closed. In the case where the doors have
constant pressure closing operation, the opposite door should remain
open until constant pressure is applied to the door close button to
close the door.
MCE has discovered that elevators with constant pressure door
closing operation AND walk through doors at the main or
alternate fire floor will automatically close the door that requires
constant pressure for closure. This can cause an unsafe
situation.
Software for controllers shipped after 1/1/2002 has been
corrected. Any products shipped prior to this date must be updated
and inspected for proper operation.
Action
If you have cars with BOTH constant pressure closing operation
AND walk through doors at the main or alternate fire floor,
immediately call MCE Technical Support to obtain updated software.
You do not need to go to the job site. Just call with your
job number. MCE will verify whether a software change is required
and make arrangements to provide the necessary update.
Help
Should you require additional technical assistance:
- Telephone 916/463-9200
- Touch "6" for Technical Support
- Refer to the reference number
above
|